Fire door inspection requirements: 2026 update

The Fire Safety (England) Regulations 2022 introduced mandatory fire door inspection frequencies for multi-occupied residential buildings. This article explains who is responsible, what inspections must cover, and how often they must take place.

Based on Fire Safety (England) Regulations 2022 and NFPA 80.

Inspection frequency

Required inspection intervals by building type

Building type Common areas Flat entrance doors Standard
Residential buildings ≥ 11 m Quarterly Annual (seek access) Fire Safety (England) Regulations 2022
Residential buildings < 11 m As per fire risk assessment As per fire risk assessment RRO 2005 / fire risk assessment
Non-domestic premises (UK) Annual minimum N/A RRO 2005 / BS 9999
All buildings (US) Annual Annual NFPA 80

What changed in 2022

The Fire Safety (England) Regulations 2022 were introduced partly in response to findings from the Grenfell Tower Inquiry, which identified systematic failures in fire door maintenance in high-rise residential buildings. The key new requirements are: (1) quarterly checks of fire doors in common parts of buildings 11 metres and above; (2) annual checks of flat entrance doors, requiring responsible persons to seek access from residents; (3) mandatory provision of fire safety information to residents.

For context on what fire doors do and what ratings mean, see our fire door glossary entry. For workplace fire safety obligations including fire wardens, see the fire warden duties guide.

What a compliant inspection record looks like

The fire log should include a record for each door inspection covering: the date of inspection; the identity of the inspector (name or role); each door inspected (location or identifier); the condition found (pass / defect identified); and for defects, the action taken and target completion date. The Fire Door Inspection Scheme (FDIS) offers a competent person register and documentation templates that satisfy the regulatory requirement.

The 3 mm gap check

A fire door is non-compliant if the gap between door leaf and frame exceeds 3 mm. Test with a pound coin (2.8 mm thick) or a standard 3 mm feeler gauge on all four sides. A gap wider than this indicates the door, frame, or seals need attention. This is the single most common defect found in fire door audits.

Fire door compliance FAQ

Questions about fire door inspection requirements