⚠ Emergency: If fire is in the building — close all fire doors and follow the escape route. Fire doors with intumescent strips buy you time.

Glossary — Passive Fire Protection

Intumescent Strip

An intumescent strip is a passive fire protection product fitted to fire doors that expands when heated to seal the gap between door and frame, preventing the passage of flames and fire gases. Required on all FD30S and FD60S fire doors. Works without power or activation — it responds directly to heat from a fire.

Fire doors Passive protection FD30S / FD60S

How it works

At ambient temperature, an intumescent strip is a thin, inert insert in the door edge or frame rebate. When a fire develops and temperatures at the door gap reach approximately 150–200°C, the intumescent material undergoes rapid expansion — typically tripling or quadrupling in thickness — to fill the gap completely. This physical seal prevents flames and hot gases from passing through the door edge gap, maintaining the door's fire resistance rating.

Intumescent strip types

Type Expands in fire Smoke-sealed Use case Location
Intumescent only Yes (at ~150–200°C) No FD30 (fire integrity only) — no smoke seal required Edge of door leaf or rebate of frame
Intumescent + cold smoke seal Yes Yes (at ambient temperature) FD30S and FD60S — smoke control required Combined product fits in single rebate groove
Intumescent threshold seal Yes Combined Bottom of door where threshold gap exceeds 3 mm Door bottom rail or threshold sill
Intumescent letter box seal Yes Yes (combined product) Letter plate openings in flat entrance fire doors Around letter plate aperture

Intumescent strips and fire door certification

A fire door is tested and certified as a complete assembly: door leaf, frame, hinges, hardware, seals, and glazing all tested together. Changing any component — including the intumescent strip — for one not specified in the door's certification can invalidate the third-party certification. The BWF-Certifire scheme and other third-party certification bodies specify which seals are acceptable for each certified door assembly.

See our fire door safety guide and our fire door glossary entry for the full six-point check and certification requirements.

Intumescent strips in fire stopping

Intumescent products are also used in fire stopping applications — sealing service penetrations through compartment walls and floors. Intumescent collars are fitted around plastic pipes passing through compartment walls; when the plastic pipe melts and collapses in a fire, the collar expands inward to seal the hole. This is a critical and frequently missed element of fire stopping during construction and renovation works.

Common inspection failures

  • Strip painted over — prevents expansion; appears intact but functionally compromised
  • Strip missing from one or more edges (particularly the top of the door)
  • Strip damaged or crushed from repeated closing force (door not hung correctly)
  • Cold smoke seal element missing or removed separately from the intumescent strip
  • Wrong product used — intumescent-only strip where combined smoke seal is required (FD30S)

These failures are flagged in fire door inspections under the fire door gap tolerances guide.

Frequently asked questions

FAQ